Technical data:
▸ Maximum operating pressure (buffer): 5 bar
▸ Maximum operating temperature (buffer): +95°C
▸ Maximum operating pressure (domestic water heat exchanger): 6 bar
▸ Maximum operating temperature (domestic water heat exchanger): +95°C
▸ Maximum operating pressure (solar heat exchanger): 12 bar
▸ Maximum operating temperature (solar heat exchanger): +110°C
▸ Number of screw-in options for heating elements: 4 pieces
Dimensions buffer tank:
600 liters:
▸ Storage height: 1900mm
▸ Diameter with thermal insulation: 750mm
▸ Diameter without thermal insulation: 600mm
▸ Tilting dimension: 2045mm
▸ Max. permissible temperature (buffer & domestic water heat exchanger): 95°C
▸ Maximum operating temperature (additional heat exchanger): 110°C
✓ You can optionally choose between one or two additional heat exchangers with an area of 2.1m².
800 liters:
▸ Storage height: 1815mm
▸ Diameter with thermal insulation: 1020mm
▸ Diameter without thermal insulation: 790mm
▸ Tilting dimension: 2085mm
▸ Max. permissible temperature (buffer & domestic water heat exchanger): 95°C
▸ Maximum operating temperature (additional heat exchanger): 110°C
✓ You can optionally choose between one or two additional heat exchangers with an area of 2.4m².
1000 liters:
▸ Storage height: 2065mm
▸ Diameter with thermal insulation: 1020mm
▸ Diameter without thermal insulation: 790mm
▸ Tilting dimension: 2305mm
▸ Max. permissible temperature (buffer & domestic water heat exchanger): 95°C
▸ Maximum operating temperature (additional heat exchanger): 110°C
✓ You can optionally choose between one or two additional heat exchangers with an area of 3m².
Type of insulation material:
▸ 600 liters: Polyurethane rigid foam with 95% closed cells, CFC and HCFC-free, fire resistance class B2 according to DIN 4102-1.
▸ 800 & 1000 liters: 100% recyclable polyester fiber, fire resistance class B1 according to DIN 4102-1.